CVE-2023-2637
What it is
Rockwell Automation's FactoryTalk System Services uses a hard-coded cryptographic key to generate administrator cookies. Hard-coded cryptographic key may lead to privilege escalation. This vulnerability may allow a local, authenticated non-admin user to generate an invalid administrator cookie giving them administrative privileges to the FactoryTalk Policy Manger database. This may allow the threat actor to make malicious changes to the database that will be deployed when a legitimate FactoryTalk Policy Manager user deploys a security policy model. User interaction is required for this vulnerability to be successfully exploited.
At a glance
- Exploitability
- Can be exploited locally on the machine with a low-privilege account, but needs a user to act. High risk of service disruption.
- Exploit odds
- 0.2% chance of exploitation in the next 30 days (EPSS).
- Fix
- A patch, advisory or fixed version is referenced. Upgrade or apply it.
Timeline
- PublishedDisclosed publicly on CVE.org and NVD
- Last updatedMost recent change to the record
Why it ranks here
- Exploited in the wild: no, CISA does not list it.
- Exploit odds: 0.2% in the next 30 days (EPSS).
- Severity: 7.3 HIGH (CVSS).
- Fix: a patch or advisory is linked.
Details
- Published
- Last modified
- Exploit probability
- 0.2% · EPSS, next 30 days
- Weakness
- CWE-321
- Record status
- Modified
Affected
- Rockwellautomation Factorytalk Policy Manager 6.11.0
- Rockwellautomation Factorytalk System Services 6.11.0
Attack profile CVSS 3.1 · 7.3
- Attack vector
- Local
- Complexity
- Low
- Privileges needed
- Low
- User interaction
- Required
- Scope
- Changed
- Confidentiality
- Low
- Integrity
- Low
- Availability
- High
Raw vector
CVSS:3.1/AV:L/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:H
Is it in your code?
Hand this to your coding agent. It searches your project for the affected products and checks versions. Nothing leaves your machine.
Read https://cve-list.com/agent/cve/CVE-2023-2637.md and follow it. Check whether this project is affected by CVE-2023-2637. Read only. Don't change anything and don't upload my code. Tell me yes, no or not sure, with the file as proof.
Fix and advisories
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1139683
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1139683