The Omron SYSMAC Nx product family PLCs (NJ series, NY series, NX series, and PMAC series) through 2022-005-18 lack cryptographic authentication. These PLCs are programmed using the SYMAC Studio engineering software (which compiles IEC 61131-3 conformant POU code to native machine code for execution by the PLC's runtime). The resulting machine code is executed by a runtime, typically controlled by a real-time operating system. The logic that is downloaded to the PLC does not seem to be cryptographically authenticated, allowing an attacker to manipulate transmitted object code to the PLC and execute arbitrary machine code on the processor of the PLC's CPU module in the context of the runtime. In the case of at least the NJ series, an RTOS and hardware combination is used that would potentially allow for memory protection and privilege separation and thus limit the impact of code execution. However, it was not confirmed whether these sufficiently segment the runtime from the rest of the RTOS.
At a glance
- Exploitability
- Can be exploited over the network without logging in. High risk of data exposure, data tampering, service disruption.
- Exploit odds
- 1.1% chance of exploitation in the next 30 days (EPSS).
- Fix
- No patch or advisory is linked yet. Look at mitigations or restrict exposure.
Timeline
- ReservedThe CVE id was reserved by its CNA
- PublishedDisclosed publicly on CVE.org and NVD
- Last updatedMost recent change to the record
Why it ranks here
- Exploited in the wild: no, CISA does not list it.
- Exploit odds: 1.1% in the next 30 days (EPSS).
- Severity: 9.8 CRITICAL (CVSS).
- Fix: none linked yet, which raises it.
Details
- Published
- Last modified
- Exploit probability
- 1.1% · EPSS, next 30 days
- Weakness
- CWE-347
- Record status
- Modified
Affected
- Omron nx701-1600 Firmware < 1.29
- Omron nx701-1620 Firmware < 1.29
- Omron nx701-1700 Firmware < 1.29
- Omron nx701-1720 Firmware < 1.29
- Omron nx701-z600 Firmware < 1.29
- Omron nx701-z700 Firmware < 1.29
- Omron nj101-1000 Firmware < 1.49
- Omron nj101-1020 Firmware < 1.49
Attack profile CVSS 3.1 · 9.8
- Attack vector
- Network
- Complexity
- Low
- Privileges needed
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- High
- Availability
- High
Raw vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H