CVE-2022-30320
What it is
Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a Saia Burgess Controls (SBC) PCD S-Bus weak credential hashing scheme issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication is done by using the S-Bus 'write byte' message to a specific address and supplying a hashed version of the password. The hashing algorithm used is based on CRC-16 and as such not cryptographically secure. An insecure hashing algorithm is used. An attacker capable of passively observing traffic can intercept the hashed credentials and trivially find collisions allowing for authentication without having to bruteforce a keyspace defined by the actual strength of the password. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
At a glance
- Exploitability
- Can be exploited from the same network segment without logging in. Limited direct impact.
- Exploit odds
- 0.3% chance of exploitation in the next 30 days (EPSS).
- Fix
- No patch or advisory is linked yet. Look at mitigations or restrict exposure.
Timeline
- PublishedDisclosed publicly on CVE.org and NVD
- Last updatedMost recent change to the record
Why it ranks here
- Exploited in the wild: no, CISA does not list it.
- Exploit odds: 0.3% in the next 30 days (EPSS).
- Severity: 4.3 MEDIUM (CVSS).
- Fix: none linked yet, which raises it.
Details
- Published
- Last modified
- Exploit probability
- 0.3% · EPSS, next 30 days
- Weakness
- CWE-327 · Broken cryptographic algorithm
- Record status
- Modified
Affected
- Honeywell Saia pg5 Controls Suite
Attack profile CVSS 3.1 · 4.3
- Attack vector
- Adjacent network
- Complexity
- Low
- Privileges needed
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- Low
- Integrity
- None
- Availability
- None
Raw vector
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N