CVE-2021-31885
What it is
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus ReadyStart V4 (All versions < V4.1.1), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). TFTP server application allows for reading the contents of the TFTP memory buffer via sending malformed TFTP commands. (FSMD-2021-0009)
At a glance
- Exploitability
- Can be exploited over the network without logging in. High risk of data exposure.
- Exploit odds
- 1.2% chance of exploitation in the next 30 days (EPSS).
- Fix
- A patch, advisory or fixed version is referenced. Upgrade or apply it.
Timeline
- PublishedDisclosed publicly on CVE.org and NVD
- Last updatedMost recent change to the record
Why it ranks here
- Exploited in the wild: no, CISA does not list it.
- Exploit odds: 1.2% in the next 30 days (EPSS).
- Severity: 7.5 HIGH (CVSS).
- Fix: a patch or advisory is linked.
Details
- Published
- Last modified
- Exploit probability
- 1.2% · EPSS, next 30 days
- Weakness
- CWE-805
- Record status
- Modified
Affected
- Siemens Capital Vstar
- Siemens Nucleus Net
- Siemens Nucleus Readystart v3 < 2017.02.4
- Siemens Nucleus Readystart v4 < 4.1.1
- Siemens Nucleus Source Code
- Siemens Apogee Modular Building Controller Firmware
- Siemens Apogee Modular Equiment Controller Firmware
- Siemens Apogee Pxc Compact Firmware
Attack profile CVSS 3.1 · 7.5
- Attack vector
- Network
- Complexity
- Low
- Privileges needed
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- None
- Availability
- None
Raw vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Is it in your code?
Hand this to your coding agent. It searches your project for the affected products and checks versions. Nothing leaves your machine.
Read https://cve-list.com/agent/cve/CVE-2021-31885.md and follow it. Check whether this project is affected by CVE-2021-31885. Read only. Don't change anything and don't upload my code. Tell me yes, no or not sure, with the file as proof.
Fix and advisories
- https://cert-portal.siemens.com/productcert/pdf/ssa-044112.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-114589.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-044112.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-114589.pdf
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-044112.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-114589.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-845392.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-044112.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-114589.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-845392.pdf