CVE-2020-25180
What it is
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.
At a glance
- Exploitability
- Can be exploited over the network without logging in, but needs a user to act. High risk of data exposure.
- Exploit odds
- 1.2% chance of exploitation in the next 30 days (EPSS).
- Fix
- A patch, advisory or fixed version is referenced. Upgrade or apply it.
Timeline
- PublishedDisclosed publicly on CVE.org and NVD
- Last updatedMost recent change to the record
Why it ranks here
- Exploited in the wild: no, CISA does not list it.
- Exploit odds: 1.2% in the next 30 days (EPSS).
- Severity: 5.3 MEDIUM (CVSS).
- Fix: a patch or advisory is linked.
Details
- Published
- Last modified
- Exploit probability
- 1.2% · EPSS, next 30 days
- Weakness
- CWE-321
- Record status
- Modified
Affected
- schneider-electric Easergy t300 Firmware ≤ 2.7.1
- schneider-electric Easergy c5 Firmware < 1.1.0
- schneider-electric Micom c264 Firmware < d6.1
- schneider-electric Pacis Gtw Firmware 5.1
- schneider-electric Pacis Gtw Firmware 5.2
- schneider-electric Pacis Gtw Firmware 6.1
- schneider-electric Pacis Gtw Firmware 6.3
- schneider-electric Saitel Dp Firmware ≤ 11.06.21
Attack profile CVSS 3.1 · 5.3
- Attack vector
- Network
- Complexity
- High
- Privileges needed
- None
- User interaction
- Required
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- None
- Availability
- None
Raw vector
CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:N/A:N
Is it in your code?
Hand this to your coding agent. It searches your project for the affected products and checks versions. Nothing leaves your machine.
Read https://cve-list.com/agent/cve/CVE-2020-25180.md and follow it. Check whether this project is affected by CVE-2020-25180. Read only. Don't change anything and don't upload my code. Tell me yes, no or not sure, with the file as proof.
Fix and advisories
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04
References
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131699
- https://www.cisa.gov/uscert/ics/advisories/icsa-20-280-01
- https://www.xylem.com/siteassets/about-xylem/cybersecurity/advisories/xylem-multismart-rockwell-isagraf.pdf
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04
- https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131699
- https://www.cisa.gov/uscert/ics/advisories/icsa-20-280-01
- https://www.xylem.com/siteassets/about-xylem/cybersecurity/advisories/xylem-multismart-rockwell-isagraf.pdf