CVE-2019-6572
What it is
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The affected device offered SNMP read and write capacities with a publicly know hardcoded community string. The security vulnerability could be exploited by an attacker with network access to the affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
At a glance
- Exploitability
- Can be exploited over the network without logging in. High risk of data exposure, data tampering.
- Exploit odds
- 2.7% chance of exploitation in the next 30 days (EPSS).
- Fix
- A patch, advisory or fixed version is referenced. Upgrade or apply it.
Timeline
- PublishedDisclosed publicly on CVE.org and NVD
- Last updatedMost recent change to the record
Why it ranks here
- Exploited in the wild: no, CISA does not list it.
- Exploit odds: 2.7% in the next 30 days (EPSS).
- Severity: 9.1 CRITICAL (CVSS).
- Fix: a patch or advisory is linked.
Details
- Published
- Last modified
- Exploit probability
- 2.7% · EPSS, next 30 days
- Weakness
- CWE-200 · Information exposure
- Record status
- Modified
Affected
- Siemens Simatic Hmi Comfort Panels Firmware < 15.1
- Siemens Simatic Hmi Comfort Outdoor Panels Firmware < 15.1
- Siemens Simatic Hmi Ktp Mobile Panels ktp400f Firmware < 15.1
- Siemens Simatic Hmi Ktp Mobile Panels ktp700 Firmware < 15.1
- Siemens Simatic Hmi Ktp Mobile Panels ktp700f Firmware < 15.1
- Siemens Simatic Hmi Ktp Mobile Panels ktp900 Firmware < 15.1
- Siemens Simatic Hmi Ktp Mobile Panels ktp900f Firmware < 15.1
- Siemens Simatic Wincc \(tia portal\) < 15.1
Attack profile CVSS 3.1 · 9.1
- Attack vector
- Network
- Complexity
- Low
- Privileges needed
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- High
- Availability
- None
Raw vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
Is it in your code?
Hand this to your coding agent. It searches your project for the affected products and checks versions. Nothing leaves your machine.
Read https://cve-list.com/agent/cve/CVE-2019-6572.md and follow it. Check whether this project is affected by CVE-2019-6572. Read only. Don't change anything and don't upload my code. Tell me yes, no or not sure, with the file as proof.
Fix and advisories
- https://cert-portal.siemens.com/productcert/pdf/ssa-804486.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-804486.pdf
References
- http://www.securityfocus.com/bid/108412
- https://cert-portal.siemens.com/productcert/pdf/ssa-804486.pdf
- https://www.us-cert.gov/ics/advisories/ICSA-19-134-09
- http://www.securityfocus.com/bid/108412
- https://cert-portal.siemens.com/productcert/pdf/ssa-804486.pdf
- https://www.us-cert.gov/ics/advisories/ICSA-19-134-09