CVE-2019-10934
What it is
A vulnerability has been identified in TIA Portal V14 (All versions), TIA Portal V15 (All versions < V15.1 Update 7), TIA Portal V16 (All versions < V16 Update 6), TIA Portal V17 (All versions < V17 Update 4). Changing the contents of a configuration file could allow an attacker to execute arbitrary code with SYSTEM privileges. The security vulnerability could be exploited by an attacker with a valid account and limited access rights on the system. No user interaction is required. At the time of advisory publication no public exploitation of this security vulnerability was known.
At a glance
- Exploitability
- Can be exploited locally on the machine with a low-privilege account. High risk of data exposure, data tampering, service disruption.
- Exploit odds
- 0.4% chance of exploitation in the next 30 days (EPSS).
- Fix
- A patch, advisory or fixed version is referenced. Upgrade or apply it.
Timeline
- PublishedDisclosed publicly on CVE.org and NVD
- Last updatedMost recent change to the record
Why it ranks here
- Exploited in the wild: no, CISA does not list it.
- Exploit odds: 0.4% in the next 30 days (EPSS).
- Severity: 7.8 HIGH (CVSS).
- Fix: a patch or advisory is linked.
Details
- Published
- Last modified
- Exploit probability
- 0.4% · EPSS, next 30 days
- Weakness
- CWE-22 · Path traversal
- Record status
- Modified
Affected
- Siemens Totally Integrated Automation Portal ≤ 17
Attack profile CVSS 3.1 · 7.8
- Attack vector
- Local
- Complexity
- Low
- Privileges needed
- Low
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- High
- Availability
- High
Raw vector
CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
Is it in your code?
Hand this to your coding agent. It searches your project for the affected products and checks versions. Nothing leaves your machine.
Read https://cve-list.com/agent/cve/CVE-2019-10934.md and follow it. Check whether this project is affected by CVE-2019-10934. Read only. Don't change anything and don't upload my code. Tell me yes, no or not sure, with the file as proof.
Fix and advisories
- https://cert-portal.siemens.com/productcert/pdf/ssa-629512.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-629512.pdf