CVE-2018-11452
What it is
A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.33), Firmware variant PROFINET IO for EN100 Ethernet module (All versions), Firmware variant Modbus TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions < V1.22). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the EN100 communication module if oscillographs are running. A manual restart is required to recover the EN100 module functionality. Successful exploitation requires an attacker with network access to send multiple packets to the EN100 module. As a precondition the IEC 61850-MMS communication needs to be activated on the affected EN100 modules. No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.
At a glance
- Exploitability
- Can be exploited over the network without logging in. High risk of service disruption.
- Exploit odds
- 2.4% chance of exploitation in the next 30 days (EPSS).
- Fix
- A patch, advisory or fixed version is referenced. Upgrade or apply it.
Timeline
- PublishedDisclosed publicly on CVE.org and NVD
- Last updatedMost recent change to the record
Why it ranks here
- Exploited in the wild: no, CISA does not list it.
- Exploit odds: 2.4% in the next 30 days (EPSS).
- Severity: 7.5 HIGH (CVSS).
- Fix: a patch or advisory is linked.
Details
- Published
- Last modified
- Exploit probability
- 2.4% · EPSS, next 30 days
- Weakness
- CWE-20 · Improper input validation
- Record status
- Modified
Affected
- Siemens dnp3 Tcp Firmware
- Siemens Iec 61850 Firmware < 4.33
- Siemens iec104 Firmware
- Siemens Modbus Tcp Firmware
- Siemens Profinet Io Firmware
- Siemens cp100 Firmware < 7.80
- Siemens cp200 Firmware
- Siemens cp300 Firmware < 7.80
Attack profile CVSS 3.0 · 7.5
- Attack vector
- Network
- Complexity
- Low
- Privileges needed
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- None
- Integrity
- None
- Availability
- High
Raw vector
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Is it in your code?
Hand this to your coding agent. It searches your project for the affected products and checks versions. Nothing leaves your machine.
Read https://cve-list.com/agent/cve/CVE-2018-11452.md and follow it. Check whether this project is affected by CVE-2018-11452. Read only. Don't change anything and don't upload my code. Tell me yes, no or not sure, with the file as proof.
Fix and advisories
- https://cert-portal.siemens.com/productcert/pdf/ssa-325546.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-635129.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-325546.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-635129.pdf
References
- https://cert-portal.siemens.com/productcert/pdf/ssa-325546.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-635129.pdf
- https://www.securityfocus.com/bid/106221
- https://cert-portal.siemens.com/productcert/pdf/ssa-325546.pdf
- https://cert-portal.siemens.com/productcert/pdf/ssa-635129.pdf
- https://www.securityfocus.com/bid/106221